This premium performance 6V dry series battery is equipped with an AP & 5/16” Stud terminal type and has more capacity than traditional lead-acid batteries, even in extreme conditions. All RELiON R4000 batteries have installation flexibility. These non-hazardous, clean batteries emit no gasses during normal operation. They can be used safely near sensitive equipment or people.
Electrical Specifications |
|
---|---|
Nominal Voltage | 6 V |
Capacity @ C100 | 424 Ah |
Capacity @ C20 | 400 Ah |
Capacity @ C10 | 360 Ah |
Capacity @ C5 | 331 Ah |
Capacity @ 75A | 270 min |
Capacity @ 25A | 915 min |
Energy @ C100 | 2544 Wh |
Internal Resistance | 1.69 mΩ |
Short Circuit Current | 4500 A |
Self Discharge | <3% per Month |
Mechanical & Physical Specifications |
|
---|---|
Dimensions (L x W x H) | 11.61 x 7.09 x 16.9” 295 x 180 x 428 mm |
Weight | 119.5 lbs (54.2 kg) |
Terminal Type | AP & 5/16” Stud |
Terminal Torque AP | 44 - 62 in-lbs (5 - 7 N-m) |
Terminal Torque STUD | 120 - 180 in-lbs (14 - 20 N-m) |
Battery Type | VRLA |
Case Material | Polypropolyene |
Handle | Rope with plastic grip |
Charge Specifications |
|
---|---|
Recommended Charge Current | 40 - 80 A |
Maximum Charge Current | 100 A |
Temperature Specifications |
|
---|---|
Operation/Storage Temperature Range | -4 - 122 ºF (-20 - 50 ºC) |
Compliance Specifications |
|
---|---|
Shipping Classification | UN 2800, CLASS 8 |
Charge Storage (12 V System) |
|
---|---|
Bulk/Absorption | 14.4 V - 14.7 V |
Float | 13.6 - 13.8 V |
Charge Storage (24 V System) |
|
---|---|
Bulk/Absorption | 28.8 V - 29.4 V |
Float | 27.2 - 27.6 V |
Charge Storage (36 V System) |
|
---|---|
Bulk/Absorption | 43.2 V - 44.1 V |
Float | 40.8 - 41.4 V |
Charge Storage (48 V System) |
|
---|---|
Bulk/Absorption | 57.6 V - 58.8 V |
Float | 54.4 - 55.2 V |
Charge Temperature Compensation |
|
---|---|
Cold Temperature Charging | +2.8 mV/cell/ºF +5 mV/cell/ºC |
Hot Temperature Charging | -2.8 mV/cell/ºF -5 mV/cell/ºC |